Chapter 8. Operating
8-4
Manually Activating a NAC/Relay
Follow these steps to manually turn a NAC or Relay on or
off, or set it to automatic operation.
1. Press <MENU>.
2. Press <NEXT> until Control/View is shown.
3. Press <ENTER>. Use the <NEXT> or <PREV> key to
select NAC or Relay.
4. Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points for NAC or Relay.
5. Press <ENTER> when the point you want to turn on or
off is displayed.
6. Press <NEXT> until a prompt similar to the following is
shown.
ENTER = Control AUX
TROUBLE STEADY
7. Press <ENTER>. The following prompt appears.
ENTER = Accept
FN: ON
8. Use <NEXT> to select one of the following:
ON. Use this option to turn the relay or NAC on. To
return the NAC/Relay to automatic operation, first
set it to OFF, and then reselect the point and set it to
AUTO.
OFF. Turns the relay or NAC off.
AUTO. Use this option to return the NAC or Relay
to automatic operation.
Enabling or Disabling Points
Use the following steps to enable or disable points.
1. Press <MENU>.
2. Press <NEXT> until Control/View is shown.
3. Press <ENTER>. Use the <NEXT> or <PREV> key to
select IDC, NAC, or Relay.
4. Press <ENTER>. Use the <NEXT> or <PREV> key to
scroll through the list of points.
5. Press <DISABLE/ENABLE> when the point you want
to turn enable/disable is displayed. A prompt similar to
the following appears.
IDNet1
FN: [Enable]
6. Use NEXT to toggle between Enable and Disable. Press
<ENTER>. A prompt appears asking you to confirm the
operation. Press <ENTER>. Keep the following in mind
when enabling/disabling points.
When a monitor point is disabled, any status
changes occurring on the point are ignored by the
panel. If a control point is disabled, any automatic
functions are inhibited. A disable trouble will exist
for each disabled point in the system.
When a monitor point is enabled, a 30-second
countdown will start to prevent an operator from
accidentally enabling a point that will alarm the
system. The point may be enabled immediately by
pressing <ENTER>, or the enable can be aborted
by pressing <EXIT>.
Control Functions
User control functions, such as Drill, City Disconnect, Con-
trol Point Bypass, and Elevator Recall Bypass are available
by pressing the <FUNCTION> key.
The table below shows the operations available in the Func-
tion menu.
Output
(LED)
a. Press <ENTER> to view a descrip-
tion of the first system point in the
list. Press NEXT to scroll through the
list of points.
System
Point
a. Press <ENTER> to view a descrip-
tion of the first system point in the
list. Press NEXT to scroll through the
list of points.
Table 8-2 Additional Point Information (Continued)
Table 8-3 Control Functions
Function Description
Drill Activates the drill operation (all notifica-
tion appliances)
Manual Evacu-
ation
Activates manual evacuation (general
alarm)
City/DACT
Disconnect
Disconnects the city circuit or DACT
(causes a trouble)
Technical Manuals Online! - http://www.tech-man.com