Chapter 6. Manually Programming Annunciators
6-6
Programming Panel and LCD LEDs
This section describes programming the built-in LEDs on 
the front panel and on the LCD annunciator. Programming 
involves setting the reference point, mode (the point and 
point state that triggers the LED to illuminate), and the color 
of the LED. 
Setting LED Color
1. Follow Steps 1 through 4 in “Accessing Annunciator 
Menus” earlier in this chapter. Choose User SW/LED 
as the type of device to program.
<ENTER>=Accept
Prg: [User SW/LED]
2. Press <ENTER>. A scrollable list of points appears. 
Use the <NEXT> and <PREV> keys to scroll to the 
point you want to edit. The display appears similar to 
the following.
User LED 1
Y LED 1/5
3. Press <ENTER>. Use the <NEXT> and <PREV> keys 
to scroll through the options until [FUNCTION] is 
shown. 
User LED 1
Fn: [Function]
4. Press <ENTER>. A prompt similar to the following 
appears, allowing you to set the LED color.
User LED 1
[Y LED]
5. Use the <NEXT> and <PREV> keys to toggle between 
the following LED colors
• Y - Programs LED as a yellow LED.
• RG - Programs LED as a Red / Green LED. If you 
assign this type to LED1 (top LED), its color will 
be red. If you assign this type to the LED2 (middle) 
or LED3 (bottom), its color will be green.
6. Press <ENTER> to choose a color. A prompt appears 
asking you to press <ENTER> to confirm the choice. 
For Canadian applications, LED colors must comply with 
Table 6-5.
List - General 
Alarm Points
List contains all zones with FIRE, VERIF, 
or STYLEC function type. Monitoring the 
Fire or Trouble state of this list allows 
you to illuminate an LED when any zone 
in the list enters an alarm or trouble 
state. Select either FIRE or TRBL as the 
mode.
List - Water-
flow Zones
List contains all zones with WATER or 
WSO function type. Monitoring the Fire 
or Trouble state of this list allows you to 
illuminate an LED when any zone in the 
list enters an alarm or trouble state. Use 
output mode to select which state (Fire, 
Trouble) is monitored.
List - Sprinkler 
Zones
List contains all zones with SO or WSO 
function type. Monitoring the Fire, Trou-
ble, or Supervisory state of this list 
allows you to illuminate an LED when 
any zone in the list enters an alarm, 
trouble, or supervisory state. Select 
either FIRE, TRBL, or SUPV as the 
mode.
Alarm Group
1 -99
Separate list for each alarm group. Mon-
itoring the Fire, Supervisory, Trouble, or 
ON state of an alarm group list allows 
you to illuminate an LED if any point in 
the group enters the fire, trouble, super-
visory, or ON state. Use output mode to 
select state monitored.
NACs 1 - 4
Separate list for each NAC. Monitoring 
the ON or trouble state of a NAC allows 
you to illuminate an LED if the NAC 
enters trouble state or turns on. Use out-
put mode to select state (on or trouble) 
monitored.
Table 6-4  Common LED Reference Points  (Cont’d)
Reference
Point
Description
Table 6-5  ULC LED Color Requirements
Function Color
Alarm Inputs Red
Alarm Signal Red with unique identifier
Signal Circuit Fault Yellow
Inhibit Yellow
Supervisory Inputs Yellow with unique identi-
fier
Power - ON Green
Trouble Signal Yellow
Alarm Signal Silence Yellow
Technical Manuals Online! - http://www.tech-man.com