Chapter 6. Manually Programming Annunciators
6-6
Programming Panel and LCD LEDs
This section describes programming the built-in LEDs on
the front panel and on the LCD annunciator. Programming
involves setting the reference point, mode (the point and
point state that triggers the LED to illuminate), and the color
of the LED.
Setting LED Color
1. Follow Steps 1 through 4 in “Accessing Annunciator
Menus” earlier in this chapter. Choose User SW/LED
as the type of device to program.
<ENTER>=Accept
Prg: [User SW/LED]
2. Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
point you want to edit. The display appears similar to
the following.
User LED 1
Y LED 1/5
3. Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the options until [FUNCTION] is
shown.
User LED 1
Fn: [Function]
4. Press <ENTER>. A prompt similar to the following
appears, allowing you to set the LED color.
User LED 1
[Y LED]
5. Use the <NEXT> and <PREV> keys to toggle between
the following LED colors
Y - Programs LED as a yellow LED.
RG - Programs LED as a Red / Green LED. If you
assign this type to LED1 (top LED), its color will
be red. If you assign this type to the LED2 (middle)
or LED3 (bottom), its color will be green.
6. Press <ENTER> to choose a color. A prompt appears
asking you to press <ENTER> to confirm the choice.
For Canadian applications, LED colors must comply with
Table 6-5.
List - General
Alarm Points
List contains all zones with FIRE, VERIF,
or STYLEC function type. Monitoring the
Fire or Trouble state of this list allows
you to illuminate an LED when any zone
in the list enters an alarm or trouble
state. Select either FIRE or TRBL as the
mode.
List - Water-
flow Zones
List contains all zones with WATER or
WSO function type. Monitoring the Fire
or Trouble state of this list allows you to
illuminate an LED when any zone in the
list enters an alarm or trouble state. Use
output mode to select which state (Fire,
Trouble) is monitored.
List - Sprinkler
Zones
List contains all zones with SO or WSO
function type. Monitoring the Fire, Trou-
ble, or Supervisory state of this list
allows you to illuminate an LED when
any zone in the list enters an alarm,
trouble, or supervisory state. Select
either FIRE, TRBL, or SUPV as the
mode.
Alarm Group
1 -99
Separate list for each alarm group. Mon-
itoring the Fire, Supervisory, Trouble, or
ON state of an alarm group list allows
you to illuminate an LED if any point in
the group enters the fire, trouble, super-
visory, or ON state. Use output mode to
select state monitored.
NACs 1 - 4
Separate list for each NAC. Monitoring
the ON or trouble state of a NAC allows
you to illuminate an LED if the NAC
enters trouble state or turns on. Use out-
put mode to select state (on or trouble)
monitored.
Table 6-4 Common LED Reference Points (Cont’d)
Reference
Point
Description
Table 6-5 ULC LED Color Requirements
Function Color
Alarm Inputs Red
Alarm Signal Red with unique identifier
Signal Circuit Fault Yellow
Inhibit Yellow
Supervisory Inputs Yellow with unique identi-
fier
Power - ON Green
Trouble Signal Yellow
Alarm Signal Silence Yellow