Chapter 2. Installation/System Checkout
2-17
Testing Circuit Supervision
Use the following procedures to confirm that IDNet and 
NACs and are supervising for opens, shorts and grounds. 
The right column in this table shows the LEDs that illumi-
nate when an open, short, or ground occurs on a specific cir-
cuit.
Replacing Lithium Battery
The panel uses a lithium battery to maintain non-volatile 
memory on the panel. In the event of a total power-down 
(AC power and lead-acid battery), the lithium battery allows 
the panel to maintain all historical logs, time/date informa-
tion, list of disabled points, and the alarm verification tallies.
Important Note: The lithium battery must be replaced only 
by a qualified service technician. 
Periodic Testing and Maintenance
The minimum requirements for periodic testing of the fire 
alarm system are outlined in chapter 10 of NFPA-72, 2002 
edition. Local codes may require additional testing and 
maintenance. All system components must be tested in 
accordance with governing codes. Specific details on select 
system components are provided below.
Battery Tests
The batteries used with the 4008 FACP are sealed lead-acid 
type. Batteries should be installed within six months of the 
date of manufacture. 
Batteries should be tested by discharging them with a suit-
able tester and verifying that battery voltage is at least 21V 
when fully discharged. Battery discharge tests should be per-
formed annually, and batteries should be replaced no longer 
than 4 years from date of installation. 
The battery charger is temperature-compensated per battery 
manufacturer recommendations. There is no charger voltage 
adjustment. At normal room temperature, battery voltage 
should be 27-27.6V when the battery set is fully charged. At 
higher temperatures, the voltage will be lower. At lower 
temperatures, the voltage will be higher. The battery charger 
has a negative temperature coefficient. At higher tempera-
tures, the chemical process in the battery is accelerated. This 
means that the ideal charger voltage is lower. Likewise, at 
lower temperatures, a higher output voltage is required for 
full charge. Control of battery charge voltage relative to 
ambient temperature prolongs battery life. The chart below 
shows the proper range of battery voltage across the speci-
fied operating range of the equipment. The chart is for 12-
cell battery sets, with nominal 24V rating.
Table 2-5  Testing Circuit Supervision
Condition Corresponding LEDs
To create an open:
Class A or B Circuit. Disconnect the 
“out” wiring from any device.
Illuminates the System Trouble 
LED. 
To create a short:
Apply a zero ohm jumper across 
the IDNet terminal blocks, or across 
the loop +/- terminals on a device.
Illuminates the System Trouble 
LED.
To create an Earth ground:
Place a 10K or smaller value resis-
tor from supervised wiring to Earth 
ground.
Illuminates the System Trouble 
LED.
If you have programmed a front 
panel or annunciator LED to detect 
Earth ground conditions, the pro-
grammed LED also illuminates. 
Refer to “Common LED Applica-
tions” in Chapter 6 of this manual 
for information on programming an 
Earth Fault LED.
Table 2-6  Temperature Effect on Batteries
Temp 
(C)
Temp 
(F)
V/cell 
(min)
V/cell 
(max)
Min. 
Battery 
Voltage
Max. 
Battery 
Voltage
0 32 2.294 2.367 27.53 28.40
5 41 2.284 2.352 27.41 28.22
10 50 2.274 2.337 27.29 28.04
15 59 2.264 2.322 27.17 27.86
22.2 72 2.250 2.300 27.00 27.60
25 77 2.244 2.292 26.93 27.50
30 86 2.234 2.277 26.81 27.32
35 95 2.224 2.262 26.69 27.14
40 104 2.214 2.247 26.57 26.96
45 113 2.204 2.232 26.45 26.78
49 120.2 2.196 2.220 26.36 26.64
Technical Manuals Online! - http://www.tech-man.com