8-1
Normal Operation
The 4008 operator interface shows the following under normal condi-
tions:
Green AC power LED is on steady
All other panel indicator LEDs are off
Front panel LCD shows the following:
SYSTEM NORMAL
1:45:07 pm 3/10/03
LAMP Test
Lamp Test is accomplished during normal monitoring (Access Level 1)
by pressing the Function key, then pressing ENTER. All LEDs energize
and all LED segments are written to.
Abnormal Conditions
Abnormal conditions are indicated on the 4008 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The tone-alert
pulses for an alarm condition, and is on steady for a trouble or supervi-
sory. If the "Display First Alarm" option is selected, the display pro-
vides information about the first, highest-priority alarm in the system
without operator intervention. If "Display First Alarm" is not selected, a
screen showing the overall system status is shown:
FIRE | SUPV | TRBL
02 | 00 | 00
When the appropriate Acknowledge key is pressed, the tone-alert turns
off and the indicator LED illuminate steady, indicating that the operator
has acknowledged all events in that category. The first abnormal point
in that category is then shown on the display:
CORE 1 MEZZANINE
FIRE 1/2
In This Chapter
Normal Operation. . . . . . . . . . . . . . . . . . . . . . .8-1
LAMP Test . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
Abnormal Conditions . . . . . . . . . . . . . . . . . . . .8-1
Silencing Alarms . . . . . . . . . . . . . . . . . . . . . . .8-2
System Reset. . . . . . . . . . . . . . . . . . . . . . . . . .8-2
Historical Logs . . . . . . . . . . . . . . . . . . . . . . . . .8-2
Viewing and Controlling Points. . . . . . . . . . . . .8-3
Enabling or Disabling Points . . . . . . . . . . . . . .8-4
Control Functions . . . . . . . . . . . . . . . . . . . . . . .8-4
Setting the Time and Date . . . . . . . . . . . . . . . .8-5
Reports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-5
Chapter 8. Operating