Chapter 6. Manually Programming Annunciators
6-9
2. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the
Supv Ack key.
<ENTER>=Accept
SUPV ACK: [Yes]
3. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the Tbl
Ack key.
<ENTER>=Accept
TROUBLE ACK: [Yes]
4. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the Sys-
tem Reset key.
<ENTER>=Accept
SYSTEM RESET: [Yes]
5. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. Press <NEXT> to see the following prompt,
which asks if you want to require the key to use the
Alarm Silence key.
<ENTER>=Accept
ALARM SILENCE: [Yes]
6. Use the <NEXT> and <PREV> keys to toggle between
Yes and No. Press <ENTER> when the correct value
appears. When you press <NEXT>, a prompt appears
asking you to press <ENTER> to save the changes.
<ENTER>=Save
Press <ENTER> to save the changes. Press <EXIT/
CLEAR> to abandon the changes.
Saving Changes to the Job
When all annunciator programming is complete, press the
EXIT/CLEAR key until the following prompt is shown.
[Cont] Dscrd Save
Use the right arrow key to move the cursor to one of the fol-
lowing options and press <ENTER>.
Cont - continues the edit session.
Dscrd - exits the edit session without saving your
changes (keeps the job that was loaded before you
started editing).
Save - saves your edit changes
Note: Both discard and save restart the panel.