Chapter 2. Installation/System Checkout
2-4
IDNet Ferrite Bead
IDNet wiring attached to TB 2-1 and 2-2 must pass through
a ferrite bead. Wrap the wiring twice through the ferrite
bead, as shown in Figure 2-5.
Compatible Devices for use with IDNet Monitor
ZAMs
A Zone Addressable Module (ZAM) allows the following
non-IDNet devices to be wired to the addressable channel.
Wiring 4098-9682 Four-Wire Base
When the 4098-9682 base is used, the auxiliary 24V power
must be routed through TEPG-US Model Number 2098-
9735 end-of-line relay, as shown in Figure 2-6.
Figure 2-5 Ferrite Bead
Table 2-1 Two Wire Devices for use with 4090-9106
Class A ZAM and 4090-9101 Class B ZAM
Head Base(s)
Max. #
Devices
4098-9685 N/A 20
4098-9612 to -
9615
4098-9788, -9683,
-9684
20
4098-9601, -9602,
-9605
4098-9788, -9683
20
Table 2-2 Four Wire Devices for use with 4090-9101
Class B ZAM
Head Base(s)
Max. #
Devices
4098-9612 to -
9615
4098-9682 (See
below for wiring.)
20
4098-9601, -9602,
-9605
4098-9682 (See
below for wiring.)
20
Figure 2-6 Wiring 4098-9682 Four Wire Base
24 VDC power
from listed FACP
END-OF-LINE DEVICE
SELECTED PER ZONE
CIRCUIT
(RELAY SHOWN
ENERGIZED)
YELLOW
YELLOW
TYPICAL 4-WIRE ZONE
24VDC DEVICES
TYPICAL 4-WIRE
DETECTOR
24VDC
RED
BLACK
E.O.L. RELAY
2098-9735
4090-9101
ZAM