Chapter 3. Auto-Programming
3-4
NAC, Relay, and Signal Circuit Output Mode
Assignments
Table 3-3 lists the default output mode (steady, temporal,
etc.) assignments for the NAC, Relay, and Signal circuits.
The output mode is a programmable attribute and it can be
manually changed, as described in Chapter 5 of this manual.
Annunciator Defaults
Annunciator cards found during the Auto-Program process
are added into the default configuration.
LCD Annunciators are configured to receive all events.
Refer to Chapter 6 for information on manually pro-
gramming which events are received by the LCD
Annunciator.
LED Annunciators and 24-I/O modules are not pro-
grammed for default operation.
DACT Defaults
The defaults for the DACT are listed below. Refer to Chap-
ter 5for information on manually programming the DACT.
Tone else pulse dialing
AC Fail reporting delay is 6 hours
Reporting format is CID
Primary and Secondary Phone Number. There are no
values for the primary and secondary phone numbers or
account codes.
The CID Group and CID Point Identifier default to the
IDNet device address.
Default event codes are shown in Table 3-4.
*Any other trouble not specifically mentioned would have a code of 330.
For example, a trouble on an output device would report an event code of 330.
SIGNAL OTS General Alarm Signal (on-til-silence)
ISOL ISOL IDNet loop isolator
SIG1-2 OTS General Alarm Signal (on-til-silence)
SIG3-4 OTR General Alarm Signal (on-til-reset)
AUX1 OTR General Alarm Relay (on-til-reset)
AUX2 TRBL Trouble Relay (on-til-clear)
Table 3-3 Default NAC, Relay, Signal Circuit Output
Mode Assignments
Circuit Default Output Method
SIG1-2 (NAC) Temporal Code A three pulse coding pattern
consisting of three ½ second pulses, each sep-
arated by ½ second silence. Each group of
three pulses is separated by 1.5 seconds of
silence.
SIG3-4 (NAC Synchronized. Used with visual NACs. Pro-
grams all visuals to flash simultaneously.
AUX1 & AUX2 Steady on
RELAY Modules Steady on
SIGNAL Mod-
ules
Steady on
Table 3-2 Default Function Type Assignments,
IDNet Devices, NACs, and Relays (Cont’d)
Device
Function
Type
Description
Table 3-4 Default CID Event Codes
Function Type Fire Supervisory Trouble
FIRE 110 - 330
WATER 113 - 330
HEAT 114 - 330
DUCT 116 - 330
PULL 115 - 330
SMOKE 111 - 330
SO - 200 330
WSO 110 200 330
SUPV - 200 330
UTIL - - 330
TROUBLE - - 330
VSMOKE 111 - 330
LATSUPV - 200 330
STYLEC 110 - 330
OTHER TRBL* - - 330