EasyManua.ls Logo

Simplex 4008-9101 - Page 42

Simplex 4008-9101
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4. Manually Programming IDNet Points
4-4
Edit IDNet Function Type
The panel’s addressable channel supports the following
function types.
Input function types are used with monitor points.
The function type determines the way in which the
panel responds to a change in a point’s electrical state.
For example, when you assign the SMOKE function
type to a smoke detector, the system interprets an open
on the device as a trouble and a short/abnormal state as
a fire. Refer to Table 4-3 for a list of input function
types and states.
Output Function Types are used with notification
appliances and relays (connected via a 4090-9007 Sig-
nal IAM). An output point’s function type determines
the operation of the NAC or relay (e.g., on til silence; on
til reset, etc.) Refer to Table 4-4 for a list of output func-
tion types. Notification appliances and relays controlled
via a 4090-9007 Signal IAM or 4090-9002 Relay IAM
activate with a steady output; coding of notification
appliances and relays attached to IAMs is not allowed.
Program the input and output function types as follows:
1. Follow the steps outlined in “Accessing IDNet Pro-
gramming Menus” earlier in this chapter. Select “Edit”
and then press <ENTER>. The display shows the first
point in the list. For example:
IDNet: 1
Pull Lobby Door
2. Use the <NEXT> and <PREV> keys to scroll through
the list of points until the appropriate point is displayed.
Press <ENTER>. A prompt similar to the following
appears.
IDNet: 1
F: [Hardware Type]
3. Use the <NEXT> and <PREV> keys to scroll through
the options until [Function] is displayed and then press
ENTER. A prompt similar to the following appears,
allowing you to select the applicable function.
IDNet: 1
[PULL]
4. Use the <NEXT> and <PREV> keys to scroll through
the list of available function types. The list of displayed
function types depends on the hardware type assigned to
the point.
5. Press <ENTER> when the appropriate function type is
shown. The system prompts you to confirm the selec-
tion.
<ENTER>= Confirm
[PULL]
6. <ENTER> will select the function in the display, while
<EXIT/CLEAR> will return to the previous screen
without making any changes
Note: Refer to table at top of Page 4-1 for UL 864 compliant
options.
4090-9116
Addressable Isolator
ISOL
4090-9101
Class B Zone Addressable Module for monitor
devices
MBZAM
4090-9106
Class A Zone Addressable Module (ZAM) for
monitor devices
MAZAM
4099-9010 Single action pull station
4099-9012 Dual Action (Push/Pull)
Addressable Pull Stations
ADRPUL
Table 4-2 Hardware Types, IDNet Modules
Module
Use this
Hardware
Type
Table 4-3 Input Function Types
Function
Type
Device State = Status
SMOKE
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with smoke detectors.
HEAT
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with heat detectors.
PULL
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with pull stations.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Related product manuals