Simplex 4020 - SECTION 6 - NETWORK INTERFACE

Simplex 4020
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4020 OPERATORS MANUAL Page 25
Document No: 4020-M010 1st February, 1997 Issue 2.0
ZONE
TYPE
DESCRIPTION
LATCHING
Noalm
Non-alarm point
YES
V-
Smoke
Smoke detector zone with alarm verification
YES
Smoke
Smoke detector zone
YES
N/L30
Non-latch AS1668 zone with 30 sec cycle
NO
N/L60
Non-latch AS1668 zone with 60 sec cycle
NO
V-Heat
Thermal detector zone with alarm
verification
YES
Heat
Thermal heat detector zone
YES
FSW
Flow switch zone
YES
MCP
Manual call point zone
YES
Valve
Valve monitor zone
YES
PSW
Pressure switch zone
YES
SPKLR
Sprinkler alarm zone
YES
V+MCP
Combination Zone of Verified Smoke
Detectors and Manual Call Points.
Manual Call Points in Alarm will bypass
alarm verification cycle.
YES
NL ALM
None latching Alarm Zone. Alarm will appear
in the Alarm list as long as the alarm
condition is present
NO
Table 1.1 INPUT ZONE DEVICE TYPES