2-3
 
 
The following procedure is required only for Revision 1.01.01 firmware in the 
4005, 4020, 4100, and 4120 panels. 
 
1.  Follow the installation procedures described in the appropriate section of 
this chapter, but do not connect the RINGx (RED) wires from each of the 
two TELCO cables.  
2.  Install the DACT programmer cable and have the terminal ready. 
3.  Power up the system.  The green LED (PWR/COMM) on the DACT will 
blink for approximately 11 minutes.  During this time you will not be able to 
program the DACT.   
4.  (4005 installations only)  Program your system to enable the DACT/City 
option and make any other panel programming changes. 
5.  (4005 installations only)  Exit the programming mode. 
6.  Watch the DACT LEDs.  Once the green and yellow LEDs turn on together, 
you will have about 30 seconds to enter the DACT programming mode from 
the terminal.  Program the DACT as described in the programing section of 
this manual.  The exception is that you will connect the RINGx (RED) wires 
from each of the two TELCO cables before exiting the DACT programmer. 
 
 
Revision-Specific Installations, Continued 
4005 and 4020/4100/4120 
Installations