2-8
Note: If your 4005 panel has firmware that is at Revision 1.01.01, read the
4005 and 4020/4100/4120 Installations section (on page 2-3) before
starting the procedure below.
1. (If applicable) Disconnect one of the two battery terminals; then remove AC
power at the power source.
2. (If applicable) Disconnect and remove the optional City Card(s). Tie off
and remove the City Circuit wiring.
3. Using four screws (provided), secure the CCDACT to its bracket (also
provided), then mount the bracket either behind the front panel display or
elsewhere in the panel as shown. (For wiring information, refer to Wiring
the 4020-0153 CCDACT into the System, which follows this section.)
Figure 2-5. Installing a 4020-0153 CCDACT Kit
Continued on next page
Installing the 4020-0153 CCDACT Kit
Mounting into the 4020 Panel
REGISTRATION LABE
L
BRACKET
CCDACT
CCDACT
AND BRACKET