2-6
Note: If your 4005 panel has firmware that is at Revision 1.01.01, read the
4005 and 4020/4100/4120 Installations section (on page 2-3) before
starting the procedure below.
1. (If applicable) Disconnect one of the two battery terminals. Then remove
AC power at the power source.
2. (If applicable) Disconnect and remove the optional City Card(s). Remove
the City bracket. Tie off and remove the City Circuit wiring.
3. Using the two screws (provided), mount the bracket (also provided) to the
chassis.
4. Snap the CCDACT onto the bracket.
5. Affix the telephone line registration label (supplied) to the FACP enclosure
at the location shown.
Figure 2-3. Installing a 4005-9810 CCDACT Kit
Continued on next page
Installing the 4005-9810 CCDACT Kit
Mounting into the 4005 Panel
REGISTRATION LABEL
BRACKET
CCDACT