3-4
With the DACT Programmer screen displaying ,
program the CCDACT as follows:
Note: Time and date must be reentered any time that power is removed
from the CCDACT.
1. Press [↵] or [↓]. Screen displays:
Type in the current time.
2. Press [↵] or [↓]. Screen displays:
Type in today’s date.
Note: The CCDACT must be programmed with an account number and
a working Central Station telephone number for proper operation.
3. Press [↵] or [↓]. Screen displays:
Type in Phone #1’s number (18 digits maximum).
Note: Phone numbers 1 or 2 may require the following special characters:
• "B" = Use in lieu of "∗" (DTMF only)
• "C" = Use in lieu of "#" (DTMF only)
• "D" = Enters 3-second delay
• “E" = Enters "wait for dial tone" command
4. Press [↵] or [↓]. Screen displays:
Type in Phone #2's number (18 digits maximum).
5. Press [↵] or [↓]. Screen displays:
Scroll to the desired format.
Continued on next page
Programming the CCDACT
Programming
02>DATE
[1/1/96]
03>PHONE #1
[ ]
01>TIME (24 HOUR)
[00:00]
04>PHONE #2
[ ]
05>COMM FORMAT #1
[4/2]
00>DACT PROGRAMMER
[REVISION X.XX.XX]