8 Operation
SMA Solar Technology AG
Operating manual EDMM-10-BE-en-27 51
In systems with a superordinate and subordinate SystemManagers, all subordinate
SystemManagers must first be commissioned to be able to integrate them into the system of the
superordinate SystemManager. To subsequently use a SystemManager or a superordinate
SystemManager as a subordinate SystemManager, the product must be reset to the default
settings.
System Manager
Select the option SystemManager in the installation assistant if you use the DataManager as a
stand-alone device without other subordinate DataManagers for open-loop or closed-loop control
of your system.
Superordinate System Manager
Select the option Superordinate systemmanager in the installation assistant if you use the
DataManager as a superordinate device with other subordinate DataManagers for open-loop or
closed-loop control of your system. With this option, the superordinate DataManager forwards the
open-loop or closed-loop control commands to the subordinate DataManager via Modbus. For
this, subordinate DataManagers must be integrated as Modbus devices into the system of the
superordinate DataManager. Meters at the grid-connection point must be connected to the
superordinate DataManager. The Modbus server must be activated in the superordinate
DataManager.
Subordinate System Manager
Select the option Subordinate systemmanager in the installation assistant if you want to use the
DataManager as subordinate device. With this option, the subordinate DataManager receives the
open-loop and closed-loop control commands of a superordinate device. These commands are
forwarded as open-loop control commands to the connected devices. In systems with a
superordinate DataManager, all subordinate SystemManagers must first be commissioned to be
able to integrate them into the system of the superordinate DataManager. To do this, select the
operating mode Control and the signal source Modbus for the subordinate DataManager.
8.7 Speedwire Encryption of the System Communication
Speedwire encryption is used to encrypt system communication between all compatible Speedwire
devices. In order to be able to use the Speedwire encryption in the system, all connected
Speedwire devices, apart from the SMA Energy Meter, must support the SMA Speedwire
Encrypted Communication function.
Speedwire encryption for systems with one Data Manager
In systems with more than one Data Manager, there can be overlaps in the system encryption.
• Only enable the Speedwire encryption in systems with one Data Manager.
Requirements:
☐ All devices in the local network must be in operation and connected to the product via an
Internet router.
☐ All devices must support the Speedwire encryption.