8 Operation
SMA Solar Technology AG
Operating manualEDMM-10-BE-en-2752
Procedure:
1. Log into the user interface.
2. Select the menu item Device administration in the menu Configuration.
3. Select the button.
4. Select SMA Speedwire devices and confirm with [Next].
All SMA Speedwire devices in the systems are searched for and displayed.
5. Enable SMA Speedwire encryption and select [Continue].
6. Assign a new system password and select [Save].
8.8 Switching Digital Outputs Based on Thresholds
The digital outputs of connected I/O systems can be switched depending on measured values or
states. In this way, heat pumps or relays, for example, can be controlled by specifying a defined
output. A tolerance (hysteresis) dependent on the selected operator prevents the digital outputs
from switching even with slight power fluctuations.
Operator Tolerance (hysteresis)
Greater than or equal to (>=) ± 0.5 %
Less than or equal to (<=) ± 0.5 %
Equal to ± 5 %
The following limiting values and parameters are available:
Alarm in case of warning or error
Alarm in case of error
System active power
System reactive power
System active power at point of interconnection (grid feed-in)
System reactive power at the point of interconnection
Reactive power setpoint
Setpoint of active power limitation
System-wide state of charge of batteries (SOC)
Active access through direct selling
Mean or peak value of the 3 voltages at the point of interconnection (depending on activation
and settings of function Q(U))
Requirements:
All devices in the local network must be in operation and connected to the product via an
Internet router.
Procedure:
1. Log into the user interface of the DataManager.
2. Select the menu item Grid management services in the menu Configuration.
3. Select the button To the configuration in the Assigning analog outputs row.