Parameter List Overview SMA Solar Technology AG
164 SI2012_2224-TEN082311 Technical Description
130# Meter External
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Description
131# Meter Total
131 01 TotExtPwrAt kW Total effective power of external sources
131 02 TotExtCur A Total current of external sources
131 03 TotExtPwrRt kVAr Total reactive power of external sources
132# State Grid
132 01 GdRmgTm hhmmss remaining time of GdValTm parameter (valid grid
time) (hhmmss)
133# State Gen
133 01 GnDmdSrc
None
Bat
Lod
Tim
Run1h
Start
ExtSrcReq
Source or generator request:
= no request
= dependent on battery state of charge
= load-dependent
= time-controlled
= for 1 hour
= started manually
= external source request
133 02 GnStt
Off
Init
Idle
Warm
Connect
Run
Retry
Disconnect
Cool
Lock
Fail
FailLock
Reinit
generator state:
= switched off
= waiting for request (ready)
= warming-up
= connecting
= operation
= restart
= disconnecting
= cooling down
= locked after operation
= error
= locked after error
133 03 GnRmgTm hhmmss remaining operating time of generator
(minimum operating time) (hhmmss)
133 04 GnRnStt Off
On
State Generator Response Master (DigIn)
134# Meter Device
134 01 ExtPwrAt kW active power of external source
134 02 ExtVtg V voltage of external source
134 03 ExtCur A current of external source
134 04 ExtFrq Hz frequency of external source