SMA Solar Technology AG Parameter List Overview
Technical Description SI2012_2224-TEN082311 173
242 05 Lod1Tm1Str hhmmss 0 Loadshed 1 time1
(begin time1, end time2)
242 06 Lod1Tm2Str hhmmss 0 Loadshed 1 time2
(begin time2, end time1)
242 07 Lod2SocTm1Str % 30 SOC limit for load shedding 2 start for t1
242 08 Lod2SocTm1Stp % 50 SOC limit for load shedding 1 stop for t1
242 09 Lod2SocTm2Str % 30 SOC limit for load shedding 2 start for t2
242 10 Lod2SocTm2Stp % 50 SOC limit for load shedding 2 stop for t2
242 11 Lod2Tm1Str hhmmss 0 Loadshed 2 time1
(begin time1, end time2)
242 12 Lod2Tm2Str hhmmss 0 Loadshed 2 time2
(begin time2, end time1)
243# Relay Timer
243 01 RlyTmr1StrDt yyyymmdd 20060101 Starting date timer1
243 02 RlyTmr1StrTm hhmmss 0 Startzeit für Relaissteuerung
Timer1
243 03 RlyTmr1Dur hhmmss 0 Operating time for relay control timer 1
243 04 RlyTmr1Cyc Single
Dayly
Weekly
Single Repeat cycle time for timer 1
243 05 RlyTmr2StrDt yyyymmdd 20060101 Starting date timer2
243 06 RlyTmr2StrTm hhmmss 0 Startzeit für Relaissteuerung Timer2
243 07 RlyTmr2Dur hhmmss 0 Operating time for relay control timer 2
243 08 RlyTmr2Cyc Single
Dayly
Weekly
Single repeated cycle time for timer 2
Menu
nr.
Parame
ter.Nr.
Parameter Name Range/Unit Default
value
Description