Page #18 background imageLoading...
Page #18 background image
APC615 Pump Unit Controller User Manual
APC615 Pump Unit Controller Version 1.0 2017-10-20 Page 18 of 54
No.
Function
Cable Size
Description
9
Aux. Output 3
1.5mm
2
see Table 10.
10~19
NC
20
Aux. Output 4
1.5mm
2
Relay normally open volt free contactor
with rated 7A, volt free output.
21
1.5mm
2
22
Aux. Output 5
1.5mm
2
Relay normally open volt free contactor
with rated 7A, volt free output.
23
1.5mm
2
24
Aux. Output 6
1.5mm
2
Normally close output with rated 7A
25
1.5mm
2
Relay common point
26
1.5mm
2
Normally open output with rated 7A
27
ECU CAN L
0.5mm
2
120Ω impedance shielded wire is recommended to use, and
single-end earthed.
28
ECU CAN H
0.5mm
2
29
ECU SCR
/
30
Charging Generator
D+ Input
1.0mm
2
Connect to D+ (WL) terminal of charging generator, if there is
no this terminal in the charger, this terminal is suspended.
31
Speed Sensor Input
0.5mm
2
Connect to speed sensor of engine, shield line is
recommended to use.
32
Speed sensor input,
internal of controller
has connected with
B-
0.5mm
2
33
Temperature sensor
1.0mm
2
Connected to temp. sensor
(Resistor/current type)
Detailed setting
items please to
see Table 12.
34
Fuel level sensor
1.0mm
2
Connected to fuel level sensor
(Resistor/current type)
35
Oil pressure sensor
1.0mm
2
Connected to oil pressure sensor
(Resistor/current/voltage type)
36
Outlet Pressure
Sensor Input
1.0mm
2
Connected to outlet pressure sensor of
pump unit (Resistor/current/voltage
type)
37
Flexible Sensor 1
1.0mm
2
User-defined (Resistor/current/voltage
type)
38
Flexible Sensor 2
1.0mm
2
User-defined (Resistor/current/voltage
type)
39
DC5V
1.0mm
2
Supply power for voltage type sensor.
40
Sensor COM
1.0mm
2
Sensor common port, internal of controller has connected
with B-.
41~45
NC
/
/
46
Emergency Stop
0.5 mm
2
Controller emergency stop the genset if input port is active.
47
Aux. Input 1(A)
0.5 mm
2
Ground connected is active (B-)