HGM6100LT Series Genset Controller User Manual Page 25 of 50
No.
Items
Range
Default
Description
73(68)
Generator Poles
(2-64)
4
Number of magnetic poles, used for
calculating speed of engine without speed
sensor.
74(69)
Temp. Sensor Open
Circuit Action
(0-2)
1
0: Not used; 1: Warn; 2: Shutdown
75(70)
Oil Pressure Sensor
Open Circuit Action
(0-2)
1
76(71)
Disconnect Oil
Pressure Delay
(0-20.0)s
0.0
When disconnect conditions include oil
pressure and engine oil pressure is higher
than disconnect oil pressure delay, the
genset is regarded as start successfully and
starter will disconnect.
77(72)
Scheduled Run
(0-1)
0
0: Disabled; 1: Enabled.
78(73)
Cycle Setting
(0-2)
0
Circulate condition: monthly, weekly and
daily can be selected.
Start time and duration can be set.
79(74)
Auto Start Inhibit
(0-1)
0
0: Disabled; 1: Enabled.
80(75)
Cycle Setting
(0-2)
0
Circulate condition: monthly, weekly and
daily can be selected.
Don’t start time and duration can be set.
81(76)
Over Power
(0-2)
0
0: Not used; 1: Warn; 2: Shutdown
When power is higher than preset value and
duration exceeds than delay, over power
warning is active. Return and delay value can
be set.
82(77)
Start Interface
(0-1)
0
0: Disabled; 1: Enabled
Start interface delay can be set.
83(78)
Maintenance
Password
(0-9999)
0
Enter password interface of maintenance
configuration.
84(79)
Date/Time
Set the date/time of controller.
85(80)
Flexible Sensor Curve
Type
(0-2)
0
0: User-defined temperature sensor
1: User-defined pressure sensor
2: User-defined level sensor
Choose sensor which need to be set, input
every point (8 points need to be input)
resistance and corresponding value (or
current, voltage) of curve.
86(81)
Engine Type
(0-39)
0
0: Conventional Engine.
87(82)
SPN Alarm Version
(0-3)
0
SPN Alarm Version.
88(83)
Custom Theme
(0-2)
0
0: Default Theme; 1: OEM Plant Theme;
2: Terminal User Theme
89(84)
Fuel Output Time
(1-60)s
1
It is the time of the genset fuel output during