No.
Items
Range
Default
Description
power on.
90(85)
Manual Mode ATS
(0-1)
0
0: Key Switch; 1: Auto Switch.
91(86)
Speed Raise Pulse
(0-20.0)s
0.2
It is the speed-up pulse output time, when
the unit enters the high-speed warm-up.
92(87)
Speed Drop Pulse
(0-20.0)s
0.2
It is the speed-drop pulse output time, when
the unit enters the stop idling.
93(88)
Fuel Level Low
Shutdown
(0-100)%
5
When fuel level of external level sensor falls
below the setting limit and lasts for 5s, low
fuel level shutdown alarm will be initiated; if
limit value set as 0, low fuel shutdown alarm
will not be initiated.
94(89)
ATS Open Time
(1.0-60.0)s
3.0
ATS open output time.
95(90)
Gen PT Fitted
(0-1)
0
0: Disabled; 1: Enabled. PT primary and
secondary voltage can be set.
96(91)
Mains PT Fitted
(0-1)
0
0: Disabled; 1: Enabled. PT primary and
secondary voltage can be set. HGM6110LT
is reserved and without this settings.
97(92)
Network
(0-1)
0
0: Disabled; 1: Enabled.
ETHERNET port is enabled or not.
98(93)
Cloud Monitoring
Setting
(0-1)
0
0: Disabled; 1: Enabled.
Controller is allowed to connect with cloud
monitoring platform.
99(94)
TCP/IP Modbus
Setting
(0-1)
0
0: Disabled; 1: Enabled.
Controller is allowed to connect with PC
software via ETHERNET interface.
100
(95)
Auto Obtain IP
Address
(0-1)
0
0: Disabled; 1: Enabled.
Controller is allowed to use dynamic
assigned IP address, and fixed IP is
unavailable.
101
(96)
IP Address
192.168.0.100
All Ethernet settings change (e.g. IP address,
subnet mask) are valid after re-power on.
102
(97)
Subnet Mask
255.255.255.0
103
(98)
Default Gateway
192.168.0.2
104
(99)
DNS Address
211.138.24.66
105
(100)
Cooling Fan On
Temp.
(0-255)
60
Unit:℃
106
(101)
Cooling Fan Off
Temp.
(0-255)
40
Unit:℃
107
Charger Voltage
(0-1)
0
0: Controller