HGM6100LT Series Genset Controller User Manual Page 26 of 50
0: Key Switch; 1: Auto Switch.
It is the speed-up pulse output time, when
the unit enters the high-speed warm-up.
It is the speed-drop pulse output time, when
the unit enters the stop idling.
When fuel level of external level sensor falls
below the setting limit and lasts for 5s, low
fuel level shutdown alarm will be initiated; if
limit value set as 0, low fuel shutdown alarm
will not be initiated.
0: Disabled; 1: Enabled. PT primary and
secondary voltage can be set.
0: Disabled; 1: Enabled. PT primary and
secondary voltage can be set. HGM6110LT
is reserved and without this settings.
0: Disabled; 1: Enabled.
ETHERNET port is enabled or not.
0: Disabled; 1: Enabled.
Controller is allowed to connect with cloud
monitoring platform.
0: Disabled; 1: Enabled.
Controller is allowed to connect with PC
software via ETHERNET interface.
0: Disabled; 1: Enabled.
Controller is allowed to use dynamic
assigned IP address, and fixed IP is
unavailable.
All Ethernet settings change (e.g. IP address,
subnet mask) are valid after re-power on.