No.
Items
Parameters
Defaults
Description
39.
Loss Excitation 1
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
20.0
18.0
5
1
0: Disable 1: Enable
Set value is percentage of gen rated
reactive power.
Return value is percentage of gen rated
reactive power.
Delay value
Action
40.
Loss Excitation 2
(0~1)
(0~200.0)%
(0~200.0)%
(0~3600)s
(0~7)
1
20.0
18.0
5
0
0: Disable 1: Enable
Set value is percentage of gen rated
reactive power.
Return value is percentage of gen rated
reactive power.
Delay value
Action
41.
Power Factor Low
1
(0~1)
(0~1.00)
(0~1.00)
(0~3600)s
(0~7)
1
0.70
0.75
5
1
0: Disable 1: Enable
Set value is gen power factor.
Set value is gen power factor.
Delay value
Action
42.
Power Factor Low
2
(0~1)
(0~1.00)
(0~1.00)
(0~3600)s
(0~7)
0
0.70
0.75
5
0
0: Disable 1: Enable
Set value is gen power factor.
Set value is gen power factor.
Delay value
Action
Switch Setting
1.
Close Time
(0~20.0)s
5.0
Pulse width of switch on. When it is 0, it
means output constantly.
2.
Open Time
(0~20.0)s
3.0
Pulse width of switch off. When it is 0, it
means output constantly.
3.
Check Time
(0~20.0)s
5.0
Feedback and check time of breaker close
status input.
Analog Sensor Setting
Temperature Sensor
1.
Curve Type
(0~15)
8
SGD
2.
Open Circuit
Action
(0~7)
1
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
3.
High Temp. Alarm
1 Set
(0~1)
((-50)~300)ºC
((-50)~300)ºC
(0~3600)s
(0~7)
1
98
96
3
7
0: Disable 1: Enable
Set value is engine temperature value.
Set value is engine temperature value.
Delay value
Action
4.
High Temp. Alarm
(0~1)
1
0: Disable 1: Enable