HGM9520N Genset Paralleled Controller User Manual Page 66 of 111
((-50)~300)ºC
((-50)~300)ºC
(0~3600)s
(0~7)
Set value is engine temperature value.
Set value is engine temperature value.
Delay value
Action
(0~1)
((-50)~300)ºC
((-50)~300)ºC
(0~3600)s
(0~7)
0: Disable 1: Enable
Set value is engine temperature value.
Set value is engine temperature value.
Delay value
Action
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
(0~1)
(0~1000)kPa
(0~1000)kPa
(0~3600)s
(0~7)
0: Disable 1: Enable
Set value is engine oil pressure value.
Set value is engine oil pressure value.
Delay value
Action
(0~1)
(0~1000)kPa
(0~1000)kPa
(0~3600)s
(0~7)
0: Disable 1: Enable
Set value is engine oil pressure value.
Set value is engine oil pressure value.
Delay value
Action
Flexible Sensor 1
Setting
0: Disable 1: Enable;
Temperature/pressure/fuel level sensors
are optional.
Flexible Sensor 2
Setting
0: Disable; 1: Enable;
Temperature/pressure/fuel level sensors
are optional.
Remote start (on demand).
Low oil pressure shutdown input