HGM9520N Genset Paralleled Controller User Manual Page 66 of 111
No.
Items
Parameters
Defaults
Description
2 Set
((-50)~300)ºC
((-50)~300)ºC
(0~3600)s
(0~7)
95
93
5
1
Set value is engine temperature value.
Set value is engine temperature value.
Delay value
Action
5.
Low Temp. Alarm
Set
(0~1)
((-50)~300)ºC
((-50)~300)ºC
(0~3600)s
(0~7)
0
70
75
5
1
0: Disable 1: Enable
Set value is engine temperature value.
Set value is engine temperature value.
Delay value
Action
Oil Pressure Sensor
1.
Curve Type
(0~15)
8
SGD
2.
Open Circuit Action
(0~7)
1
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
3.
Low OP Alarm 1
Set
(0~1)
(0~1000)kPa
(0~1000)kPa
(0~3600)s
(0~7)
1
103
117
2
7
0: Disable 1: Enable
Set value is engine oil pressure value.
Set value is engine oil pressure value.
Delay value
Action
4.
Low OP Alarm 2
Set
(0~1)
(0~1000)kPa
(0~1000)kPa
(0~3600)s
(0~7)
1
124
138
5
1
0: Disable 1: Enable
Set value is engine oil pressure value.
Set value is engine oil pressure value.
Delay value
Action
Fuel Level Sensor
1.
Curve Type
(0~15)
0
Not used.
Flexible Sensor 1
1.
Flexible Sensor 1
Setting
(0~1)
0
0: Disable 1: Enable;
Temperature/pressure/fuel level sensors
are optional.
Flexible Sensor 2
1.
Flexible Sensor 2
Setting
(0~1)
0
0: Disable; 1: Enable;
Temperature/pressure/fuel level sensors
are optional.
Digital Input Ports
Digital Input Port 1
1.
Contents Setting
(0~70)
31
Remote start (on demand).
2.
Active Type
(0~1)
0
0: Close 1: Open
Digital Input Port 2
1.
Contents Setting
(0~70)
27
Low oil pressure shutdown input
2.
Active Type
(0~1)
0
0: Close 1: Open
Digital Input Port 3

Table of Contents