HGM9520N Genset Paralleled Controller User Manual Page 69 of 111
No.
Items
Parameters
Defaults
Description
1
Contents Setting
(0~299)
0
Not Used.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Digital Output Port 8
1
Contents Setting
(0~299)
0
Not Used.
2
Active Type
(0~1)
0
0: Normally open; 1: Normally close
Scheduled Run
1
Scheduled Run
(0~1)
0
0: Disable; 1: Enable
Circular setting (monthly, weekly, daily),
start time setting, continuous time setting
and loading or not are available.
Scheduled Not Run
1
Scheduled Not Run
(0~1)
0
0: Disable; 1: Enable
Circular setting (monthly, weekly, daily),
non-start time setting, and continuous time
setting are available.
Maintenance Setting
1
Maintenance
(0~1)
0
0: Disable; 1: Enable
Maintenance time, alarm action can be set.
Alternative Configuration
1
Alt. Config. 1
(0~1)
0
0: Disable; 1: Enable
Power supply system, rated voltage, rated
frequency, rated speed, rated current, rated
active power, rated reactive power, GOV
SW1, AVR SW1 can be set.
2
Alt. Config. 2
(0~1)
0
0: Disable; 1: Enable
3
Alt. Config. 3
(0~1)
0
0: Disable; 1: Enable
Sync Setting
Auto Sync
1
GOV Output Type
(0~1)
1
0: Internal Relays; 1: Internal Analogue
2
GOV Reverse
(0~1)
0
0: Disable; 1: Enable
3
GOV Action
(0~2)
1
0: None; 1: Adjust to Rated; 2: Adjust Center
Point
4
AVR Output
(0~2)
2
0: None 1: Internal Relays;
2: Internal Analogue
5
AVR Reverse
(0~1)
0
0: Disable; 1: Enable
6
AVR Action
(0~2)
1
0: None; 1: Adjust to Rated; 2: Adjust Center
Point
Sync Check
1
Dead Bus Volt
(10~50)V
30
It is considered Bus no power when Bus
voltage is lower than dead Bus voltage.
2
Check Volt
(0~30)V
3
It is considered voltage synchronization
when the voltage difference between