HGM9520N Genset Paralleled Controller User Manual Page 70 of 111
Generator and Bus is lower than
synchronization voltage difference.
It is considered frequency synchronization
when the frequency difference between
Generator and Bus is less than “Check Pos
Freq” but more than “Check Neg Freq”.
It is considered ‘Check Phase Angle’ when
the initial phase difference is lower than
synchronization phase difference.
Gen initial phase will add pre-set phase
offset based on the sampling initial phase.
If sync signals are not detected during the
set “Fail Sync Delay”, controller will initiate
corresponding alarms based on the “Fail
Sync Act”.
It is the minimum MSC number.
(Not available for HGM9520N)
0: None; 1: Warning; 2: Block; 3: Safety Trip;
4: Safety Trip and Stop; 5: Trip; 6: Trip and
Stop; 7: Shutdown.
(Not available for HGM9520N)
0: 500kBit/s; 1: 250kBit/s;
2: 125kBit/s; 3: 50kBit/s.
(Not available for HGM9520N)
0: Start All; 1: Start Sets on demand
(Not available for HGM9520N)
When starting option is set as “start all”,
controller will stop corresponding gensets
as required after “Start All Time” delay.
(Not available for HGM9520N)
0: Disable; 1: Enable
(Not available for HGM9520N)
When the input is active, the controller will
start/stop the genset automatically
according to the running time and the
pre-set balanced running time.
Balance running gensets should be
configured as the same priority.
(Not available for HGM9520N)
Set the number of closed gensets on the
bus.
(Not available for HGM9520N)