HGM9520N Genset Paralleled Controller User Manual Page 73 of 111
No.
Items
Parameters
Defaults
Description
8.
DL Trip Value
(0~200)%
50
9.
DL Trip Delay
(0~3600)s
5
Heavy Load
1.
Heavy Load 1
Request Load
(0~6000)kW
400
Details of function description please see
the following description.
2.
Heavy Load 1
Rated Load
(0~6000)kW
200
3.
Heavy Load 1
Stable Delay
(0~3600)s
5
4.
Heavy Load 1 ACK
Delay
(0~3600)s
5
5.
Heavy Load 2
Request Load
(0~6000)kW
400
6.
Heavy Load 2
Rated Load
(0~6000)kW
200
7.
Heavy Load 2
Stable Delay
(0~3600)s
5
8.
Heavy Load 2 ACK
Delay
(0~3600)s
5
Sync Calibration
MSC
1.
MSC ID
(0~31)
1
It is the ID in the MSC communication
network, which indicates that the MSC ID in
the entire communication network should
be unique.
(Not available for HGM9520N)
2.
Module Priority
(0~31)
0
Smaller the value, higher the priority.
(Not available for HGM9520N)
Sync Control
1.
Slip Freq
(0~1.00)Hz
0.10
Adjust generator frequency so that gen
frequency is greater than slip frequency of
bus. Phase synchronization adjustment is
conducted when the sync difference
frequency is set to 0.
2.
Sync Freq (Volt)
(0~500)%
20
Gain(P)
(0~2000)%
20
Stability(I)
(0~2000)%
0
Rate of change (D)
3.
Sync Freq (Relay)
(0.25~4.00)Hz
1.20
Response
(0.05~1.60)s
0.20
Stability
(0~100)%
10
Gain
(0~10.0)%
1.0
Dead area
4.
Sync Volt (Volt)
(0~500)%
20
Gain(P)