HGM9520N Genset Paralleled Controller User Manual Page 74 of 111
No.
Items
Parameters
Defaults
Description
(0~2000)%
20
Stability(I)
(0~2000)%
0
Rate of change (D)
5.
Sync Volt (Relay)
(0.25~4.00)Hz
1.20
Response
(0.05~1.60)s
0.20
Stability
(0~100)%
10
Gain
(0~10.0)%
1.0
Dead area
6.
Sync Phase (Stable
Time)
(0.1~20.0)s
2.0
Sync. confirmation time during phase sync
adjustment
7.
Sync Phase (Volt)
(0~500)%
20
Gain(P)
(0~2000)%
20
Stability(I)
(0~2000)%
0
Rate of change (D)
8.
Sync Phase (Relay)
(0.25~4.00)Hz
1.20
Response
(0.05~1.60)s
0.20
Stability
(0~100)%
10
Gain
(0~10.0)%
1.0
Dead area
Load Control
1.
kW Control (Volt)
(0~500)%
20
Gain(P)
(0~2000)%
20
Stability(I)
(0~2000)%
0
Rate of change (D)
2.
kW Control (Relay)
(0.25~4.00)Hz
1.20
Response
(0.05~1.60)s
0.20
Stability
(0~100)%
10
Gain
(0~10.0)%
1.0
Dead area
3.
kvar Control (Volt)
(0~500)%
20
Gain(P)
(0~2000)%
20
Stability(I)
(0~2000)%
0
Rate of change (D)
4.
kvar Control (Relay)
(0.25~4.00)Hz
1.20
Response
(0.05~1.60)s
0.20
Stability
(0~100)%
10
Gain
(0~10.0)%
1.0
Dead area
Load
1.
Load Minimum
(0~100.0)%
1.0
It is the load percentage when the soft
unload is opened.
2.
Load Mode
(0~3)
0
0: Gen; 1: Mains;
2: Takeover; 3: Load Control.
3.
Export Mode(W)
(0~1)
0
0: Fixed Power; 1: Frequency-Power.
It is active when Load mode is Gen control
mode.
4.
Export Mode(var)
(0~1)
0
0: Fixed Power; 1: Voltage-Power.
It is active when Load mode is Gen control
mode.
5.
Export Power(W)
(0~100.0)%
30.0
It is used to load control.