EasyManua.ls Logo

SMC Networks HEC002-A5 - 2.4 Disposing of product

SMC Networks HEC002-A5
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety Instructions
HEC002-A/HEC006-A
2-6
5
Detection of
breakage of temp.
sensor
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR17)
Restart power
supply
6
Excessive temp.
increase
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display.
(ERR12)
Restart power
supply
7
Excessive temp.
decrease
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display
(ERR13)
Restart power
supply
8
Abnormal output
(Overload)
The unit continues to
operate.
Error indication on display
(ERR15)
Restart power
supply
9
Low flow rate
(Option)
Shuts off power supply to
the Heat exchanger, Pump
and Fan.
Error indication on display
(ERR16)
Restart power
supply
2.4 Disposing of product
Contact an industrial waste disposal company for disposal of the product.
To minimize the risk, drain the fluid from the product when it is scrapped. If the fluid is left inside, an
accident and damage can result during transportation.