HRX-OM-W058
Chapter 5 Display and setting of various functions
5.19 Communication function HRS-R Series
5-54
4. Select serial protocol from the table below with [▲] key or [▼] key, and confirm by
pressing “SEL”.
Table 5.19-3 List of set value
Set value
Explanation
Initial value
(Default setting)
MODBUS protocol
Simple communication protocol 1
Simple communication protocol 2
*3
*3When the setting of the contact input 2 is “Remote signal”, “Simplified communication protocol
2” cannot be set.
Communication specification Setting and checking
5. Press the [SEL] key once.
The set screen of communication specification is displayed on the digital display.
6. Select communication specification from the table below with [▲] key or [▼] key, and
confirm by pressing “SEL”.
Table 5.19-4 List of set value
Set value
Explanation
Initial value
(Default setting)
RS-232C
RS-485
RS-485 terminal Setting and checking
7. Press the [SEL] key once.
The set screen of RS-485 terminal is displayed on the digital display.
8. Select RS-485 terminal from the table below with [▲] key or [▼] key, and confirm by
pressing “SEL”.
Table 5.19-5 List of set value
Set value
Explanation
Initial value
(Default setting)
No terminal
With terminal
PV
SV
PV
SV