Chapter 5 Display and setting of various functions
5.5 Inspection monitor menu HRS-R Series
5-12
Check of the accumulated operation time of the fan motor
9. Press the [SEL] key once.
The accumulated operation time of the fun motor is displayed on the digital display.
Displays the accumulated operation time of the fan motor. Refer to Table 5.5-2 for the
display.
AL29 Fan motor maintenance alarm is generated when the accumulated operation
time of the fan motor reaches 20,000 hours ( ) or more. For details, refer to
Chapter 7 Alarm indication and trouble shooting.
Check of the accumulated operation time of the compressor
10. Press the [SEL] key once.
The accumulated operation time of the compressor is displayed on the digital display.
Displays the accumulated operation time of the compressor. Refer to Table 5.5-2 for
the display.
AL30 Compressor maintenance alarm is generated when the accumulated operation
time of the compressor reaches 50,000 hours ( ) or more. For details, refer
to Chapter 7 Alarm indication and trouble shooting.
Check of the accumulated operation time
11. Press the [SEL] key once.
The accumulated operation time is displayed on the digital display.
Displays the accumulated operation time. Refer to Table 5.5-2 for the display.