52
<(760) User operation setting>
Line of 11 points curves defined by customer is set by operating
actuator position.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Select (USEr) with the UP or
DOWN button ( ) and hold
down the set button ( ) for
1sec. or longer.
3
Select (ACT) for value setting, and
hold down the set button ( )
for 1sec. or longer.
4
Hold down the set button ( )
for 1sec. or longer with specified
input current parameter.
5
The LCD displays go (Go) for
confirmation. Confirm there are no
hazardous conditions due to the
actuator startup, and then hold
down the set button ( ) for
1sec. or longer.
6
Operate the actuator by pressing
UP or DOWN button ( ).
Check the actuator movement, and
hold down the mode button ( ) at
desired position for 1sec.
7
Pressing UP or DWON button
( ), and set input current
parameter of 10 points as clause 4
to 6.
8
Hold down the mode button ( )
again for 1sec. or longer for 3 times
with some interval.
or
or
or

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks IP8001 Series and is the answer not in the manual?

SMC Networks IP8001 Series Specifications

General IconGeneral
BrandSMC Networks
ModelIP8001 Series
CategoryValve Positioners
LanguageEnglish

Related product manuals