UPS/NTA GB/DELMP_EXPC1C3C6_B 24
3.7.2 Load transfer from inverter to mains
In the control panel of one of the units, select:
- menu "UPS SYSTEM",
- menu "UPS COMMANDS"
- and submenu "LOAD TO MAINS".
Display for the "LOAD TO MAINS" control
UPS COMMANDS: LOAD TO MAINS
CONFIRM TRANSFER TO
AUTOMATIC BYPASS
cancel validate
'ESC' 'ENTER'
Validate pressing the ENTER key.
3.7.3 Load transfer from mains to inverter
In the control panel of one of the units, select:
- menu "UPS SYSTEM",
- menu "UPS COMMANDS"
- and submenu "LOAD TO INVERTER".
Display for the "LOAD TO INVERTER" control
UPS COMMANDS: LOAD TO INVERTER
CONFIRM TRANSFER TO INVERTER
Cancel validate
'ESC' 'ENTER'
Validate pressing the ENTER key.