DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
11
DIRIS A40/A41 - Ref.: 536 103 B GB
A : NEW COMMUNICATION TABLE FROM 01/2009
2 > TABLE C650 Hex : Energy monitoring
Decimal Hex. No. of Description Unit JBUS function
address address words available
50768 C650 2 hour meter 1/100 h 3
50770 C652 2 Reserved for manufacturer - 3
50772 C654 2 Reserved for manufacturer - 3
50774 C656 2 Reserved for manufacturer - 3
50776 C658 2 Reserved for manufacturer - 3
50778 C65A 2 Reserved for manufacturer - 3
50770 C652 2 active energy + kWh 3
50772 C654 2 reactive energy + kvarh 3
50774 C656 2 apparent apparente kVAh 3
50776 C658 2 active energy - kWh 3
50778 C65A 2 active energy + kWh 3
50780 C65C 2 No. Compteurs d’Impulsions - 3
50782 C65E 2 pulse meter 1 - 3
50784 C660 2 pulse meter 2 - 3
50786 C662 2 pulse meter 3 - 3
50788 C664 2 pulse meter 4 - 3
50790 C666 2 pulse meter 5 - 3
50792 C668 2 pulse meter 6 - 3
50794 C66A 2 Reserved for manufacturer - 3
50796 C66C 2 Reserved for manufacturer - 3
50798 C66E 2 Reserved for manufacturer - 3
50800 C670 2 Reserved for manufacturer - 3
50802 C672 2 S Predicted active power kW/100 3
50804 C674 2 S Predicted reactive power kvar/100 3
50806 C676 2 S Predicted apparent power kVA/100 3
50808 C678 2 Ea+ between 2 tops 0,1 Ws 3
50810 C67A 2 Ea- between 2 tops 0,1 Ws 3
50812 C67C 2 Er+ between 2 tops 0,1 vars 3
50814 C67E 2 Er- between 2 tops 0,1 vars 3
50816 C680 2 Reserved for manufacturer - 3
50816 C680 1 Reserved for manufacturer - 3
50817 C681 1 Reserved for manufacturer - 3
3 > TABLE C750 Hex : Additional measurements allocated from CT values (current transformer) and VT
(voltage transformer) values
Decimal Hex. No. of Description Unit JBUS function
address address words available
51024 C750 2 avg U12 V/100 3
51026 C752 2 avg U23 V/100 3
51028 C754 2 avg U31 V/100 3
51030 C756 2 avg V1 V/100 3
51032 C758 2 avg V2 V/100 3
51034 C75A 2 avg V3 V/100 3
51036 C75C 2 avg F Hz/100 3
51038 C75E 2 avg I1 mA 3
51040 C760 2 avg I2 mA 3
51042 C762 2 avg I3 mA 3
51044 C764 2 avg In mA 3
51046 C766 2 avg
Σ
active power + kW/100 3
51048 C768 2 avg
Σ
active power - kW/100 3
51050 C76A 2 avg
Σ
reactive power + kvar/100 3
51052 C76C 2 avg
Σ
reactive power - kvar/100 3
51054 C76E 2 avg
Σ
apparent power kVA/100 3
51056 C770 2 max/avg U12 V/100 3
COMMUNICATION

Other manuals for socomec DIRIS A40

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DIRIS A40 and is the answer not in the manual?

socomec DIRIS A40 Specifications

General IconGeneral
TypeMultifunction Meter
DisplayLCD with backlight
Operating Temperature-10 to +55 °C
MountingPanel mounting
Measurement ParametersVoltage, Current, Power, Energy, Frequency
CommunicationRS485, Modbus RTU
Storage Temperature-25°C to +70°C
Protection DegreeIP20
StandardsIEC 61557-12
AccuracyClass 0.5
Dimensions96 x 96 mm