DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
45
DIRIS A40/A41 - Ref.: 536 103 B GB
Decimal Hexa. Number Text Unit
address address of words
COMMUNICATION
8 : ΣP+
9 : ΣQ+
10 : ΣS
11 : F
12 : ΣPFL
15 : thd I1
16 : thd I2
17 : thd I3
18 : thd U12
19 : thd U23
20 : thd U31
21 : HOUR
22 : V1
23 : V2
24 : V3
25 : thd In
26 : thd V1
27 : thd V2
28 : thd V3
29 : ΣP-
30 : ΣQ-
31 : ΣPFC
32 : T°C 1
33 : T°C 2
34 : T°C 3
35 : T°C internal
36 : ΣP predicted
37 : ΣQ predicted
38 : ΣS predicted
1362 552 2 Current alarm OUT 6 upper threshold value –
1364 554 1 Duration s.
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Alarm event log (continued)
Size of this zone : 133 words (decimal) or 83 (hexadecimal)
Table of current and voltage harmonics
Decimal Hexa. Number Text Unit
address address of words
2304 900 1 thd I1 0.10%
2305 901 1 thd I2 0.10%
2306 902 1 thd I3 0.10%
2307 903 1 thd In 0.10%
2308 904 1 thd U12 0.10%
2309 905 1 thd U23 0.10%
2310 906 1 thd U31 0.10%
2311 907 1 thd V1 0.10%
2312 908 1 thd V2 0.10%
2313 909 1 thd V3 0.10%
2314 90A 1 Harmonic I1 row 3 0.10%
2315 90B 1 Harmonic I2 row 3 0.10%
2316 90C 1 Harmonic I3 row 3 0.10%
2317 90D 1 Harmonic IN row 3 0.10%
2318 90E 1 Harmonic I1 row 5 0.10%
2319 90F 1 Harmonic I2 row 5 0.10%
2320 910 1 Harmonic I3 row 5 0.10%
2321 911 1 Harmonic IN row 5 0.10%