COMMUNICATION
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)
NB:
To reset several parameters to zero, add the corre-
spondinggureindicatedinthe“text”column.
Example: reset Max P+ and kvarh + to zero:
2 + 100 = 102 (Hex)
Example:
To reset all values for DIRIS number 5 to zero, the
following frame should be sent:
PULSE METERS VALUES
Input meters
DIRIS A40/A41 reply: identical to the message sent.
Size of this zone: 12 words (decimals) or C (hexadecimals)
Decimal Hexa. Number Text Unit
address address of words
2560 A00 2 Input E1, option ES 1
2562 A02 2 Input E2, option ES 1
2564 A04 2 Input E3, option ES 2
2566 A06 2 inputE4, option ES 2
2568 A08 2 Input E5, option ES 3
2570 A0A 2 Input E6, option ES 3
Slave
SAVED COMMAND (RESET)
The following command should be done to save
programming parameters changes for DIRIS number 5.
NB : The DIRIS A40/A41 responds with an identical frame.
Slave
05
Function
06
High-order
address
06
Low-order
address
00
Values
0000
CRC 16
88C6
05
Function
06
High-order
address
04
Low-order
address
00
High-order
word N°
10
Low-order
word N°
00
CRC 16
84BE