DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
60
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6)
Decimal Hexa. Number Text Unit
address address of words
1024 400 1 RAZ:
Max3I : 0 x 0001
MaxP+ : 0 x 0002
MaxP-: 0 x 0004
MaxQ+ : 0 x 0008
MaxQ- : 0 x 0010
MaxS : 0 x 0020
Hour meter : 0 x 0040
kWh+ : 0 x 0080
kvarh+ : 0 x 0100
kVAh : 0 x 0200
kWh- : 0 x 0400
kvarh- : 0 x 0800
All parameters : 0 x 1000
MaxU : 0 x 2000
MaxV : 0 x 4000
MaxF : 0 x 8000
1025 401 1 R.A.Z. :
E1 : 0 x 0001
E2 : 0 x 0002
E3 : 0 x 0004
E4 : 0 x 0008
E5 : 0 x 0010
E6 : 0 x 0020
Min/Max I : 0 x 0040
Min/Max In : 0 x 0080
Min/Max U : 0 x 0100
Min/Max F : 0 x 0200
Min/Max PF : 0 x 0400
Min/Max P : 0 x 0800
Min/Max Q : 0 x 1000
Min/Max thd I : 0 x 2000
Min/Max thd In : 0 x 4000
Min/Max thd U : 0 x 8000
1026 402 1 RAZ:
Min/Max thd V : 0 x 0001
Min/Max V : 0 x 0002
Min/Max S : 0 x 0004
10 alarms event log : 0 x 0008
10 voltage dips event log : 0 x 0010
10 surges event log : 0 x 0020
10 cut-offs event log : 0 x 0040
Averaged out frequencies : 0 x 0080
Averaged out voltage values : 0 x 0100
Averaged out power values : 0 x 0200
Size of this zone: 3 words (decimals) and 3 (hexadecimals)