DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
59
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
Decimal Hexa. Number Text Unit
address address of words
Size of this zone: 108 words (decimals) or 6C (hexadecimals)
1 : k
2 : M
608 260 1 Upper threshold OUT 6
609 261 1 Unit upper threshold OUT 6 :
0 : /
1 : k
2 : M
610 262 1 Hysteresis 0 to 99 OUT 6 %
611 263 1 SpeciedtimeOUT6 s.
612 264 1 Relay status OUT 6 :
0 : Open
1 : Closed
613 265 1 Voltage dips detection threshold (SAG� %
614 266 1 Voltage dip detection threshold hysteresis
(SAG� %
615 267 1
Voltage surge detection threshold hysteresis
(SWELL�
%
616 268 1 Voltage surge detection threshold hysteresis
(SWELL� %
617 269 1 Hour meter allocation
1. Auxiliary power supply
2. Currents
3. phase to phase voltage
618 26A 1 Hour meter trigger threshold A/V
619 26B 1 Reserved for manufacturer
Example:
Configuration of a 4-wired unbalanced network
(4 NBL� for DIRIS number 5.
DIRIS A40/A41 reply: Identical to message sent.
Slave
05
Function
06
High-order
address
02
Low-order
address
00
High-order
word N°
00
Low-order
word N°
05
CRC 16
49F5