DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
24
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
880 370 2 System value for current mA
882 372 2 System value for phase-to-phase voltage V/100
884 374 2 System value for phase-to-neutral voltage V/100
886 376 2 avg U12 V/100
888 378 2 avg U23 V/100
890 37A 2 avg U31 V/100
892 37C 2 avg V1 V/100
894 37E 2 avg V2 V/100
896 380 2 avg V3 V/100
898 382 2 avg F Hz/100
900 384 2 max/avg U12 V/100
902 386 2 max/avg U23 V/100
904 388 2 max/avg U31 V/100
906 38A 2 max/avg V1 V/100
908 38C 2 max/avg V2 V/100
910 38E 2 max/avg V3 V/100
912 390 2 max/avg F Hz/100
914 392 2 avg In mA
916 394 2 max/avg In mA
918 396 2
Mean positive active power between 2 signals
0.1 kW
920 398 2
Mean negative active power between 2 signals
0.1 kW
922 39A 2
Mean positive reactive power between 2 signals
0.1 kvar
924 39C 2
Mean negative reactive power between 2 signals
0.1 kvar
926 39E 2
Predicted total active power
0,1 kvar
928 3A0 2
Predicted total reactive power
0,1 kvar
930 3A2 2
Predicted total apparent power
0,1 kvar
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Address available with the Monitoring or Control/Command option (continued)
Slave
05
Function
03
High-order
address
03
Low-order
address
00
High-order
word n°
00
Low-order
word n°
9E
CRC 16
C5A2
Example:
To display all the values for DIRIS number 5 in one
inquiry, the following frame should be sent:
Zone size: 164 words (decimal) or A4 (hexadecimal).
Instant value display
Decimal Hexa. Number Text Unit
address address of words
878 36E 2
Status of inputs-outputs
0 : status input 1 (0 = open, 1 = closed�
bit 1 : status input 2 (0 = open, 1 = closed�
bit 2 : status input 3 (0 = open, 1 = closed�
bit 3 : status input 4 (0 = open, 1 = closed�
bit 4 : status input 5 (0 = open, 1 = closed�
bit 5 : status input 6 (0 = open, 1 = closed�
bit 16 : status output 1 (0 = open, 1 = closed�
bit 17 : status output 2 (0 = open, 1 = closed�
bit 18 : status output 3 (0 = open, 1 = closed�
bit 19 : status output 4 (0 = open, 1 = closed�
bit 20 : status output 5 (0 = open, 1 = closed�
bit 21 : status output 6 (0 = open, 1 = closed�