DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
84
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
3454 D7E 1 Query! : phase-to-phase residual value :
0 : no
5: U12
6: U23
7: U31
3455 D7F 2 Value
3457 D81 1 Query! : phase-to-neutral residual value :
0 : no
22 : V1
23 : V2
24 : V3
3458 D82 2 Value
3460 D84 2 Duration ms
3462 D86 1 Day
3463 D87 1 Month
3464 D88 1 Year
3465 D89 1 Hour
3466 D8A 1 Minute
3467 D8B 1 Second
Decimal Hexa. Number Text Unit
address address of words
3584 E00 1 Query! : maximum phase-to-phase value :
0 : no
5: U12
6: U23
7: U31
3585 E01 2 Value
3587 E03 1 Query! : maximum phase-to-neutral value :
0 : no
22 : V1
23 : V2
24 : V3
3588 E04 2 Value
3590 E06 2 Duration ms
3592 E08 1 Day
3593 E09 1 Month
3594 E0A 1 Year
3595 E0B 1 Hour
3596 E0C 1 Minute
3597 E0D 1 Second
LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)
Voltage dip n-10
LAST 10 VOLTAGE SURGE EVENT LOG / SWELL (FUNCTION 3)
Voltage surge n-1
Zone size: 140 words (decimal) or 8C (hexadecimal).