DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
83
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
3426 D62 1 Query! : phase-to-phase residual value :
0 : no
5: U12
6: U23
7: U31
3427 D63 2 Value
3429 D65 1 Query! : phase-to-neutral residual value :
0 : no
22 : V1
23 : V2
24 : V3
3430 D66 2 Value
3432 D68 2 Duration ms
3434 D6A 1 Day
3435 D6B 1 Month
3436 D6C 1 Year
3437 D6D 1 Hour
3438 D6E 1 Minute
3439 D6F 1 Second
Decimal Hexa. Number Text Unit
address address of words
3440 D70 1 Query! : phase-to-phase residual value :
0 : no
5: U12
6: U23
7: U31
3441 D71 2 Value
3443 D73 1 Query! : phase-to-neutral residual value :
0 : no
22 : V1
23 : V2
24 : V3
3444 D74 2 Value
3446 D76 2 Duration ms
3448 D78 1 Day
3449 D79 1 Month
3450 D7A 1 Year
3451 D7B 1 Hour
3452 D7C 1 Minute
3453 D7D 1 Second
LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)
Voltage dip n-8
Voltage dip n-9