DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
GB
79
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
LAST 10 VOLTAGE DIPS EVENT LOG / SAG (FUNCTION 3)
Voltage dip n-1
Zone size: 140 words (decimal) or 8C (hexadecimal).
Decimal Hexa. Number Text Unit
address address of words
3328 D00 1 Query! : phase-to-phase residual value :
0 : no
5: U12
6: U23
7: U31
3329 D01 2 Value
3331 D03 1 Query! : phase-to-neutral residual value :
22 : V1
23 : V2
24 : V3
3332 D04 2 Value
3334 D06 2 Duration ms
3336 D08 1 Day
3337 D09 1 Month
3338 D0A 1 Year
3339 D0B 1 Hour
3340 D0C 1 Minute
3341 D0D 1 Second
LAST 10 ALARMS EVENT LOG (FUNCTION 3)
Alarm n-10
Decimal Hexa. Number Text Unit
address address of words
32 : T°C 1
33 : T°C 2
34 : T°C 3
35 : T°C internal
36 : ΣP predicted
37 : ΣQ predicted
38 : ΣS predicted
3219 C93 2 Upper threshold value
3221 C95 1 Duration s
3222 C96 1 Day
3223 C97 1 Month
3224 C98 1 Year
3225 C99 1 Hour
3226 C9A 1 Minute
3227 C9B 1 Second