13
STATYS 200-1000A - Ref.:OPMSTA200910-GB_06
ENGLISH
Activate source 2 conduction press the key (2), the message "use S2" blinks, press the key to validate this
choice or press the key to cancel the command.
These changeovers are performed whether the sources are synchronous or asynchronous, unless the
factory setting of the device is changed to "synchronous only" mode (no asynchronous transfer, set-
tings accessible in advanced parameters, see §10).
If the sources are sliding, the appliance requests a "transfer on the fly"
Transfer on the y
If, during a conduction activation request, the sources are sliding, a "y" message blinks along with the source shift value.
The user can then:
wait for the transfer to occur automatically once the 2 sources become synchronous,
cancel using the
key and thereby return to the "y" message,
or force the transfer (if the device conguration authorises an asynchronous transfer) by once more pressing the
key for the desired source. The message "frc trf" (force transfer) blinks on the last line ("y" no longer blinks), press
the key to validate the forced transfer request.
To exit this mode, press the key for the source in conduction state once more. The message "esc" then appears.
Validate it using the key or cancel it using the key.
Stop automatic switchback when the device is waiting for phase synchronisation, press the key for the alternate
source ( or ).
The message "end asb" appears
7. mImIc paNEL