The can lead battery to leak even explode.
The current capacity of DC power cables (from battery to inverter) should be at least 90A. Use short power cables
to avoid high voltage drop & power loss.
Use a multimeter to check the batter voltage & polarity before switching ON batteries. Make sure connections
are correct according to this manual.
If you want to store the batteries without using them, they should be disconnected from ME3000SP, and be kept
in a cool, dry, and ventilated environment.
Battery maintenance operators shall have the knowledge and technical skill for battery maintenance;
All batteries connected in parallel should be of the same model, and have same firmware version. This is a design
issue needs to be considered by designer/installer, particularly when replacing batteries or modifying an existing
energy storage system.
Warning: Do not disassemble or break the battery. Its electrolyte can be toxic and damage your skin and eyes.
Warning: follow the following rules during battery installation/maintenance.
a) Take off your watch, ring, and other metal objects.
b) Only use tools with insulated handles.
c) Wear rubber gloves and shoes.
d) Do not put tools or metals above the battery.
e) Switch off ME3000SP & batteries before connecting / disconnecting battery terminals.
f) Battery positive / negative poles should be isolated from ground.