PowerMagic 400V C&I Energy Storage System User Manual
30
maintenance and quality inspection.
If special operations or work at height are required, they should report to the safety personnel
if any in advance and take precautionary measures.
In case of bad weather or unexpected situation, the work should be stopped immediately.
4.2 Foundation
4.2.1 Foundation construction requirements
Unreasonable foundation construction plan will bring more difficulties or troubles to the
placement, opening and closing of the door and later operation of the BESS. Therefore, the foundation
of the energy storage system must be designed and constructed in accordance with certain standards
beforehand, so as to meet the requirements of mechanical support, cable routing, and later
maintenance and overhaul.
Site selection requirements:
The installation location should not be in a low-lying area and the installation level should
be at least 300mm above the highest historical water level in the area.
Distance from airports, buried waste disposal sites, river banks or dams should be ≥ 2km.
Choose an open location and ensure that there are no obstacles within 10m of the site.
Considering safety, the distance between the energy storage system and residential buildings
is ≥12m, and the distance from schools, hospitals and other densely populated buildings is >30.5m,
or the distance should follow the local distance or regulation If this safety distance is not met, the
firewall between the energy storage system and the building should be built , convenient transport
Warning
As the energy storage system is heavy, the conditions of the installation site (mainly geological
and climatic conditions) should be examined in detail before the foundation is constructed. Only on this
basis can the design and construction of the foundation begin.
Integrated foundations must be used.