PowerMagic 400V C&I Energy Storage System User Manual
79
Green light flashes
Non-grid-connected but
trouble-free operation
1s on,1s off
Red light always on
Grid-side faults
Abnormalities in grid
phase, frequency,
amplitude; phase loss,
unbalance
ALARM
Red light always on
Device Alarms
DC-side faults, grid-
side faults, and alarms
generated by the PCS
itself
Red light flashing
communication alarm
1s on,1s off
Go out
No alarm
Table 6.3 High voltage box indicator status information
Type
Indicator status
Hidden meaning
Note
Green
Green light always on
Main contactor closed, manual switch QB2
disconnected
Slow flash 1Hz
BMS system powered, main contactor not closed
Flash 2Hz
The BMS system is powered, the main contactor
is closed, the manual switch QB2 is closed, and
the prompt can disconnect the manual switch
QB2
Red
Red light always on
System malfunction shutdown, relays are
disconnected
Go out
No auxiliary power on the DC side of the system
6.2 Power-on operation
The prerequisite for this part of the operation is that the storage cabinet is in a normal un-started
state, specifically all switches of the high voltage box, auxiliary power module, and system
convergence module are in the off state, the positive and negative buses of the battery clusters have
not yet been connected to the battery PACKs (this step is for the first time when the power is turned
on), and the three-phase AC input power cables are connected and have a normal voltage input.
6.2.1 Check before powering on
Before powering up the equipment, check the following items carefully.