8 Monitoring system commissioning
The monitoring system WEB interface operation includes communication cable wiring,
communication settings, login interface, home page, battery cluster information, real-time alarms,
parameter configuration, historical data, logging out and other displays or operations.
8.1 Communication cable wiring
Through the Ethernet cable, one end is connected to the WEB port on the BESS door board, and
the other end is connected to the computer 's network port to establish a communication connection
between the BESS and the computer.
The system is powered up (see the power-on step for details) to ensure that the auxiliary power
supply of the BESS is working properly (the ' POWER ' indicator light on the door panel can be
observed, and if the indicator light is on, it indicates that the auxiliary power supply is working
properly). After waiting for about 1 minute:
⚫ If the computer 's network port indicator light flashes, it indicates that the communication
between BESS and computer has been established.
⚫ If the indicator light is not on, check the network connection.
8.2 Communication settings
Change your computer's network settings. Open the Internet Protocol version 4 (TCP/IPv4)
properties page of the computer, select "Use the following IP address" and change the IP address to
192.168.1.100, change the subnet mask to 255.255.255.0, and leave the rest of the settings as default.
Click OK to complete the settings, as shown in Figure 8.1 and 8.2.
8.3 Login interface
Step 1 Open a computer browser, enter the IP address of the energy storage system
"192.168.1.100" in the search field, and click the Enter key to enter the login interface shown in Figure
8.3.