Low-current resistance measurement
Range
Resolution
Accuracy
0.0 to 199.9
0.1
(3% m.v. + 3 digits)
200 to 1999
1
Voltage at open terminals: <8V
Current at shorted terminals 5mA< I <15mA
Acoustic signal and LED lit in green for measured resistance < 30 ± 10%
Compensation of test leads resistance
11.2 Other technical specification
a) type of insulation according to IEC 61010-1 and IEC 61557 ....................................................................................... double
b) measurement category according to IEC 61010-1 .................................................................................. IV 600V (III 1000V)
c) protection class of enclosure acc. to IEC 60529 ............................................................................................................. IP67
d) power supply for the meter ....................................................................... 4 AA alkaline batteries or rechargeable batteries
e) dimensions ................................................................................................................. 220 x 100 x 60 mm / 8.7 x 3.9 x 2.4 in
f) meter weight .......................................................................................................................................... approx 0.6 kg / 1.3 lb
g) storage temperature ................................................................................................................... -20 to +70C / -4 to +158F
h) operating temperature ................................................................................................................-10 to +50C / 14 to +122F
i) humidity .................................................................................................................................................................. 20 to 90%
j) reference temperature ........................................................................................................................ +23 ± 2C / +73 ± 3F
k) reference humidity .................................................................................................................................................. 40 to 60%
l) altitude (above sea level) ......................................................................................................................... <2000 m / <6562 ft
m) display ................................................................................................................................................................ LCD segment
n) memory of measurement results ......................................................................................................... 990 cells
o) data transmission ............................................................................................................................ wireless link
p) quality standard ............................................................... development, design and manufacturing are ISO 9001 compliant
q) the device meets the requirements of the IEC 61557 standard
r) the product meets the EMC requirements (immunity for industrial environment) according to the following standards .......
............................................................................................................................................. IEC 61326-1 and IEC 61326-2-2
Note:
SONEL S.A. hereby declares that the radio device type MIC-30 complies
with Directive 2014/53/EU. The full text of the EU Declaration of Conformity is
available at the following website address: https://sonel.pl/en/download/declaration-
of-conformity/
11.3 Additional data
Data on additional uncertainties are useful mainly when the meter is used in non-standard
conditions and for metrological laboratories for the purpose of calibration.
11.3.1 Additional uncertainties according to IEC 61557-2 (R
ISO
)
Significant parameter
Designation
Additional uncertainty
Position
E
1
0%
Supply voltage
E
2
0% (BATT is not lit)
Temperature 0 to 35°C / 32 to 95°F
E
3
2%