Commissioning help
1. Set language and time
2. Commissioning help / setup wizard
a) select or
b) skip.
The setup wizard guides through the necessary basic settings in the correct
order. Every parameter is explained on the display of the controller. Pressing the
„esc“ key takes you back to the previous setting.
b) With free commissioning the settings should be made in the following order:
l menu 10. Language
l menu 3. Time, Date and Operating Times.
l Menu 5. Settings, all values
l menu 6. Protection Functions (if any adjustments necessary).
l menu 7. Special Functions (if any adjustments necessary).
3. In menu operating mode "4.1. Manual”, test the witch outputs with the con-
sumers connected and check the sensor values for plausibility. Then set to auto-
matic mode.See " Manual " on page 31
The setup wizard can be accessed in menu 7.2 at any time.
Consider the explanations for the individual parameters on the following pages and check if further settings are necessary
for your application.
1. Measurement values
Serve to display the current measured temperatures.
If ‚error‘ appears on the display instead of the measurement value,
there may be a defective or incorrect temperature sensor.
If the cables are too long or the sensors are not well-placed, small
deviations in the measurement values may occur. In this case, the dis-
play values can be compensated by adjustments in the controller See
" Sensor Calibration " on page 41. The selected program, connected
sensors and the specific model design determine which meas-
urement values are displayed.
28