Periods
Approval time for the compressor function
Here the desired periods are set in which the compressor is approved. For each weekday, three times can be specified, furthermore,
you can copy individual day to other days. The compressor is shut down outside of the set times.
Anti Legionella
See " Anti Legionella " on page 58.
Loading pump
The function switches on the charge pump of a heat pump if a heat request from the heating circuit or DHW sensor is present. This func-
tion can only be selected if a compressor was activated on a different relay.
Storage charge pump (SLP) overshoot
The pump turns off after the compressor delayed by this time.
Glycol pump
The glycol pump is turned on and off together with the compressor. Function is only visible if the additional function Compressor is activ-
ated.
Gylcol pump lag
After shutting down the compressor, the pump remains on for the time set here.