Shanghai STEP Electric Co., Ltd.
30
closes to position.
F31 = 130%, The inverter continues to close the door at the door-closing speed,
until there is a opening signal.
F32 Torque boost range0-30
Inverter torque setting, compensating torque at lower frequencyless than10Hz
Note
F31 and F32 are set based on the holding torque and rated current of
motor. If lasting too long, motor may burn out.
F33 Speed of holding Torque of door closing and openning range0-90
Set the speed when holding Torque of door closing and openningFactory setting
is 60Do not change it unless it is needed
F34 v/f compensating torque at low speed range0-30
compensating torque at low speed in mode v/f
Note
F4 is set based on the holding torque and rated current of motor. If it is
set too big , Noise of motor may occur,and if it is set too small, High speed can not
be pulled up.
F35 Set of solutuio for door-blocked range0/1/2/3/4/5
When door is blocked, inverter will work as following:
F35 = 0stop outputclosing door is forbiddenshield the closing instruction of
PC
F35 = 1shield the closing instruction of PC for 3 seconds, then respond it
F35 = 2shield the closing instruction of PC for 5 seconds, then respond it
F35 = 3shield the closing instruction of PC for 10 seconds, then respond it
F35 = 4shield the closing instruction of PC for 20 seconds, then respond it
F35 = 5shield the closing and opening instruction of PC, then execute the
openningaction in reverse automatically
Noteinverter will respond the opening instruction of PC immediately
whatever F35 is.
F36 Set input mode range00000000~11111111
Parameter F36 is binarythe 07 digit and input point INPUT0~INPUT7
correspondsetting 0short uprightmeans NO input pointsetting1long upright
means NC input point.
Note
If the control mode of inverter is V/FPlease set parameter F36 first.
For Type A1, parameters F36.0 ~ F36.2are available
others are void
For Type A2/A3, parameters F36.0 ~ F36.7are available