Shanghai STEP Electric Co., Ltd.
32
No instruction:means that inverter receives no input signals
F39 = 0,duration of No instruction is limitless;
F39 = 0.01 ~ 600.00,duration of No instruction reaches the set value,close tahe
door in low speed automatically。
F40 Protecting time of closing-blocked range:0.50-5.00
If F40 was set too small, door closing-blocked protect would work frequently,on
the contrary, door closing-blocked protect will not work
F41 Ternimals protect function range:0/1
F41 = 0 terminals protect function is available,F41 = 1 terminals protect function
is void。
F42 Gain P at low speed openning range:0-30000
Setting parameter P of door opening in low speed proportion gain in PID control
F43 Setting of parameter P range:0-30000
Setting parameter P of proportion gain in PID control
F44 Setting of parameter I range:0-30000
Setting parameter I of integral gain in PID control
F45 Setting of parameter D range:0-30000
Setting parameter D of differential time in PID control
F46 Carrying frequency range:4-12
PWM Frequency setting, the higher the PWM Frequency is, the less the inverter
noise and the better the current waving will be, but waste will go up. It can be set
according to the user’s needs.
F47 Motor poles range:2-12
Driving motor rated voltage, please set according to the nameplate parameters of
the driving motor.
F48 Rated Voltage range:200-250
Driving motor rated voltage, please set according to the nameplate parameters of
the driving motor.
F49 Motor rated speed Range range:0-3000
Driving motor rated speed, please set according to the nameplate parameters of
the driving motor.
F50 Rated current range:0.00-2.00
Driving motor rated current, please set according to the nameplate parameters of
the driving motor.
F51 Rated output torque range:0.00 ~ 3.00
Set rated output torqueof motor.
F52 Spare